Search This Blog

Wednesday 20 September 2017

TE Meter not responding


Ensure Cont & FP, ER & GF slider switches in ON
Ensure PCS is in set position & PCR relay is energised.
If PCR not energising even though BP pressure is normal contact shed for wedging PCR / using bypassing switch.
Ensure GFD & GFC contactors picked up by keeping Isolation Switch in RUN & RH in any one direction
Check power data MG Voltage & MGF current values and Torque values.

If MG field current is not more than 10 A
Check AG breakers in ECC1 & ECC2 in ON
Check AG drive shaft
Check AC control, Control, local control breakers in ON
Check GFB breaker in ON position & BS is closed condition
Check SCR connections
Recycle breakers and try
If still not rectified, contact shed

If MG field current is more than 10 A but no MG / RB output
Contact shed

If torque Reference & feedback values are different
Recycle both TCCs and try
If not successful, disable the Truck & work
After some time enable truck and try

Procedure for disabling truck
Secure Control stand
In DID, select Truck cut out
Select truck & disable

If MG output is available
Take 3 notches, check Crew message & contact shed.

On Run
Tor Ref & Feedback values will be different for different Trucks, but Same Ref & Feedback for individual Trucks

Throttle / Governor Defects
During erratic RPM / engine RPM is not matching to TH position
Check and secure amphenol plug
Check governor oil level
Change C/stand and try

Contact shed

Leave sanctioned list

THE FOLLOWING EMPLOYEES LEAVE HAS BEEN SANCTIONED/REGRETTED BY DEE/CCRC/KJM   (23.05.2019) S.N   Name of t...