Whenever system applies power restriction with TCC related message:
Back TH to Idle & resume traction after few seconds.
If not successful, isolate the defective truck & try to clear the block section if only one truck is affected
If unable to work, Stop the loco, Secure Control Stand, Recycle the TCC breakers and try
If not rectified, isolate the particular truck, & work if the train load permits.
After isolating a Truck, Inform PRC / Shed
Up to 60 % power will be available from working truck

Procedure for recycling TCCs
EMD - GTO Locos
Switch OFF Computer, TCC1, TCC2, AC GTO #1 & AC GTO #2 Breakers
Wait for 30 seconds
Switch ON AC GTO #2, AC GTO #1, TCC1, TCC2 & Computer Breakers
EMD - IGBT Locos
Switch OFF Computer, TCC, IGBT #1 PS & IGBT #2 PS Breakers
Wait for 30 seconds
Switch ON IGBT #2 PS, IGBT #1 PS, TCC & Computer Breakers

Siemens Locos
Switch OFF Computer, TCC, PS #5, Local Control & Control Breakers
Wait for 30 seconds
Switch ON Control, Local Control, PS #5, TCC & Computer Breakers

Medha Locos
Most of the faults are reset automatically by keeping TH in Idle & Isolation switch in Isolate
If fault is not reset Switch OFF Computer Breaker
Wait for 1 Minute
Switch ON Computer Breaker

Recycling of Computer Breaker should be done when Engine is running 